The flame detectors are used for the supervision of
gas flames, yellow- or blue-burning oil flames and for ignition
spark proving.
-
With this type of flame supervision, the UV radiation
emitted by gas or oil flames is used to generate the flame
signal.
-
The radiation detector consists of a UV-sensitive
cell with 2 electrodes, which ignite when illuminated with
radiation in the 190...270 nm range of the spectrum, thereby
triggering a current in the flame detector circuit.
-
The UV cell does not respond to glowing firebrick in
the combustion chamber, daylight or light from the boiler room
illumination.
Die-cast aluminium housing with a 1 in. mounting
coupling (D) and a connection facility for cooling air. The housing
of this detector has a bayonet fitting which allows it to be
secured either directly to the mounting coupling or to the glass
holder AGG06. The mounting coupling can be screwed to a viewing
tube or to the ball head AGG07. The Pg cable gland can be removed
and replaced, if some other detector cable shall be used.
|