HQXL 系列冷凝机组技术数据 /Specification of
HQXL Series Condensing Unit
|
机组型号 Model |
HQXL-13E |
HQXL-16E |
HQXL-23E |
HQXL-29E |
HQXL-41E |
||
名义输入功率(w) Nominal Input |
700 | 900 | 1200 | 1400 | 2100 | ||
电源 power Supply |
220V/50Hz | ||||||
使用工质 refrigerant(max. limit kg) |
R22(1.2) |
R22(1.5) |
R22(2.0) |
R22(2.5) |
R22(3.5) |
||
启动电流(A)start-up current | 22 | 27 | 38 | 42 | 66 | ||
**大负载电流(A)Max. Load Current |
4.0 | 5.1 | 6.5 | 7.7 | 11.2 | ||
蒸发温度范围 Evaporating Temp. |
-40 ~ -5 ℃ |
||||||
使用环境温度范围 Ambient Temp. |
0 ~ 40 ℃ |
||||||
压缩机型号 Model of Compressor | QXL-13E | QXL-16E | QXL-23E | QXL-29E | QXL-41E | ||
Condenser |
样式 Style |
翅片式 Fin Tubes |
|||||
Fan motor |
风扇直径(mm) Diameter of Fan |
300 | 300 | 300 | 350 | 400 | |
风量(m 3 /hr) Air Flow |
1300 | 1530 | 1530 | 1800 | 3000 | ||
Pipe/接管 mm |
吸气口 Gas Inlet | 12.7 | 15.88 | ||||
液体出口 Liquid Outlet |
9.52 | ||||||
外形尺寸 Outline Dimension |
长 Length(mm) |
560 | 580 | 610 | 630 | ||
宽 Width(mm) |
470 | 580 | 540 | 610 | |||
高 Height(mm) | 365 | 445 | 545 | ||||
Refrigeration Capacity 制冷量 |
蒸发温度(℃) Evaporating Temp. |
制冷量: W ( Kcal/h ) Refrigeration Capacity 冷凝温度 Condensing Temp.: 45 ℃ 环境温度 Ambient Temp.: 32 ℃ |
|||||
-40 |
410(355) |
505(434) |
670(580) | 845(730) |
1350(1160) |
||
-35 | 532(458) | 650(560) |
820(709) |
1033(893) |
1684(1444) |
||
-30 |
656(563) |
800(688) |
1005(870) |
1266(1096) |
2080(1785) |
||
-25 |
793(682) |
969(833) |
1240(1070) |
1562(1348) |
2550(2190 ) |
||
-20 |
969(833) |
1183(1017) |
1500(1295) |
1845(1593) |
3100(2670) |
||
-15 |
1164(1000) |
1421(1223) |
1840(1590) |
2263(1956) |
3740(3210) |
||
-10 |
1416(1217) |
1728(1486) |
2125(1825) |
2614(2245)
|
4490(3860) |
||
-5 |
1672(1438) |
2042(1756) |
2440(2095)
|
3010(2577) |
5350(4600) |
||
Wiring Capacity 接线容量 |
Leakage Protector |
额定电流( A ) Rated Current |
10 | 15 | 20 | ||
泄露电流( mA ) Leakage Current |
30 | ||||||
Wire Diameter 线径 (mm 2 ) |
10m 以内 |
2.0 |
|||||
20m 以内 |
2.0 |
2.5 |
|||||
30m 以内 |
2.0 |
2.5 |
|||||
注意: Notes 1. 应尽量控制冷媒充注量,**多不能超过表中值。 The refrigerant charge must be controlled strictly. The Maximize limitation of charging is listed in the table. 2. 吸气管及蒸发器管径,应考虑回油并再次确认流速后确定。 Diameter of the suction and evaporating pipes should be decided by oil circulation and reconfirmation of gas speed. 3. 替代 R12 机型时管径选择应注意保证气体流速在横管内达到 3.8m /s 以上,在竖管内达到 7.6m /s 以上。 The diameter of pipes must guarantee the gas speed of 3.8m /s through horizontal pipes and 7.6m /s through vertical ones. 4. 单侧管长应在 10m 以下,此时高差应在 3m 以下。 The single sided pipe length is 10m ; with height difference should be within 3m . |
Tel: